WAGO-I/O-SYSTEM 750 Appendix 279
750-8100 PFC100; 2ETH; ECO
Manual
Version 1.6.0, valid from FW Version 03.02.02(14)
15.1.2.8 8 Channel Digital Output Modules with Diagnostics and Input
Process Data
750-537,
753-537
The digital output modules have a diagnostic bit for each output channel. When
an output fault condition occurs (i.e., overload, short circuit, or broken wire), a
diagnostic bit is set. The diagnostic data is mapped into the Input Process Image,
while the output control bits are in the Output Process Image.
Diagnostic bit S = ‘0’ no Error
Diagnostic bit S = ‘1’ overload, short circuit, or broken wire
15.1.2.9 16 Channel Digital Output Modules
750-1500, -1501, -1504, -1505