44 Device Description WAGO-I/O-SYSTEM 750
750-8100 PFC100; 2ETH; ECO
Manual
Version 1.6.0, valid from FW Version 03.02.02(14)
3.8.8 Connection Type
Table 19: Technical Data Field Wiring
Wire connection
CAGE CLAMP
®
Cross section
0.08 mm² 2.5 mm², AWG 28 14
Stripped lengths
8 mm 9 mm / 0.33 in
Table 20: Technical Data Data Contacts
Data contacts
Slide contact, hard gold plated, self-
cleaning
3.8.9 Climatic Environmental Conditions
Table 21: Technical Data Climatic Environmental Conditions
Surrounding air temperature, operation
0 °C 55 °C
Surrounding air temperature, storage
25 °C +85 °C
Relative humidity without condensation
5 % 95 % without condensation
Operating altitude
0 2000 m
Pollution degree
2
Overvoltage category
II
Protection type
IP20
Resistance to harmful substances
Acc. to IEC 60068-2-42 and
IEC 60068-2-43
Maximum pollutant concentration at
relative humidity < 75 %
SO
2
25 ppm
H
2
S 10 ppm
Special conditions
Ensure that additional measures for
components are taken, which are used
in an environment involving:
dust, caustic vapors or gases
ionizing radiation

Table of Contents

Other manuals for WAGO PFC100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WAGO PFC100 and is the answer not in the manual?

WAGO PFC100 Specifications

General IconGeneral
BrandWAGO
ModelPFC100
CategoryController
LanguageEnglish

Related product manuals