E.6
SEL-2414 Transformer Monitor Instruction Manual Date Code 20130214
Modbus Communications
Function Code Details
Table E.14 shows the Modbus Command Region.
22–29 16–1D Pulse OUT501–OUT508 1–30 seconds Duration (Defaults to 1 second) N/A
30–37 1E–25 Pulse OUT601–OUT608 1–30 seconds Duration (Defaults to 1 second) N/A
38 26 Reset Data Regions 01—Modbus Communications Counters N/A
39 27 Control Remote
Bits 1–16
1—Set
2—Clear
3—Pulse (1 SEL
OGIC Processing Interval)
See below
40 28 Control Remote
Bits 17–32
1—Set
2—Clear
3—Pulse (1 SEL
OGIC Processing Interval)
See below
41 29 Reset Demand N/A N/A
42 2A Reset Peak Demand N/A N/A
43 2B Reset Energy N/A N/A
44 2C Reset Min/Max N/A N/A
Table E.12 Command Code Outputs (Sheet 2 of 2)
Command Code in
Decimal
Command Code
in Hex
Function Parameter 1 Parameter 2
Table E.13 Modbus Command Code Parameters
Parameter 2 for Command Code 39 Parameter 2 for Command Code 40
0000 0000 0000 0001—RB01 0000 0000 0000 0001—RB17
0000 0000 0000 0010—RB02 0000 0000 0000 0010—RB18
0000 0000 0000 0100—RB03 0000 0000 0000 0100—RB19
0000 0000 0000 1000—RB04 0000 0000 0000 1000—RB20
0000 0000 0001 0000—RB05 0000 0000 0001 0000—RB21
0000 0000 0010 0000—RB06 0000 0000 0010 0000—RB22
0000 0000 0100 0000—RB07 0000 0000 0100 0000—RB23
0000 0000 1000 0000—RB08 0000 0000 1000 0000—RB24
0000 0001 0000 0000—RB09 0000 0001 0000 0000—RB25
0000 0010 0000 0000—RB10 0000 0010 0000 0000—RB26
0000 0100 0000 0000—RB11 0000 0100 0000 0000—RB27
0000 1000 0000 0000—RB12 0000 1000 0000 0000—RB28
0001 0000 0000 0000—RB13 0001 0000 0000 0000—RB29
0010 0000 0000 0000—RB14 0010 0000 0000 0000—RB30
0100 0000 0000 0000—RB15 0100 0000 0000 0000—RB31
1000 0000 0000 0000—RB16 1000 0000 0000 0000—RB32
Table E.14 Modbus Command Region
Decimal Address HEX Address Function Code Supported Field
2000 7D0 03h, 04h, 06h, 10h Parameter 2
2001 7D1 03h, 04h, 06h, 10h Parameter 1
2002 7D2 03h, 04h, 06h, 10h Command Code