SEL-2414 Transformer Monitor Instruction Manual Date Code 20130214
SEL-2414 Transformer Monitor Command Summary
THE n Displays saved thermal monitor report n where n = 1 is the most recently saved report.
THE C Clears the hourly profile, daily profile, and thermal event data archives.
THE D x y Retrieves daily profile data from day x to day y.
THE H x y Retrieves hourly profile data from day x to day y.
If x and y are omitted, retrieves entire profile data.
If x or y is omitted, retries profile from day x (y) to present.
THE P n Loads preset value of accumulated insulation loss of life.
THE R Clears the hourly profile, daily profile, and thermal event data archives and resets the total loss-of-life values.
THE T Displays the four temperature inputs received from an SEL-2032, an SEL-2030, or an SEL-2020
Communications Processor.
TIM View time.
TIM hh:mm:ss Set time by entering TIM followed by hours, minutes, and seconds, as shown (24-hour clock).
TRI Trigger an event report data capture.
Access Level 2 Commands
ANA p t Test analog output port where p is a percentage of full scale between 0–100% and t is time in 1.0–10.0
minutes
CAL Go to Access Level C.
CON n Set, clear, or pulse an internal remote bit (n is the remote bit number from 1–32).
FIL WRITE filename Transfer settings file filename from the PC to the device.
L_D Load new firmware.
LOO Enables loopback testing of M
IRRORED BITS channels.
LOO A Enable loopback on M
IRRORED BITS Channel A for the next 5 minutes.
LOO B Enable loopback on M
IRRORED BITS Channel B for the next 5 minutes.
PAS Show existing Access Level 1 and Level 2 passwords.
PAS 1 xxxxxxxxxxxx Change Access Level 1 password to xxxxxxxxxxxx.
PAS 2 xxxxxxxxxxxx Change Access Level 2 password to xxxxxxxxxxxx.
PUL n Pulse output contact n for 1 second.
SET Enter/change devicesettings.
SET DN Enter/change DNP3 settings.
SET F Enter/change front-panel settings.
SET G Enter/change global settings.
SET L Enter/change SEL
OGIC variable and timer settings.
SET name For all SET commands, jump ahead to a specific setting by entering the setting name.
SET P n Enter/change serial Port n settings (n = 2, 3, 4, or F; if not specified, the default is the active port).
SET R Enter/change report (event and SER) settings.
SET … TERSE For all SET commands, TERSE disables the automatic SHO command after the settings entry.
STA R or C Clear self-test status and restart device.
Serial Port Command Command Description