Standard RLL
Instructions
5–116
Standard RLL Instructions
Network Instructions
In the following example when X1 is on and the module busy relay SP116 (see
special relays) is not on, the WX instruction will access port 2 operating as a master.
Ten consecutive bytes of data is read from the Master CPU and copied to V memory
locations V2000–V2004 in the slave CPU at station address 5.
DirectSOFT
Handheld Programmer Keystrokes
LD
KF205
X1
The constant value KF205
specifies the port number (2)
and the slave address (5)
LD
K10
The constant value K10
specifies the number of
bytes to be written
LDA
O 2300
WX
V2000
V2000 is the starting
location in the for the Slave
CPU where the specified
data will be written to
V2001
8534
V2002
1936
V2003
9571
V2004
1423
S
S
S
S
V1777
XXXX
V2000
3457
Master
CPU
SP116
V2005
XXXX
V2301
8534
V2302
1936
V2303
9571
V2304
1423
S
S
S
S
V2277
XXXX
V2300
3457
V2305
XXXX
Slave
CPU
Octal address 2300 is
converted to 4C0 HEX and
loaded into the accumulator.
V2300 is the starting
location for the Master CPU
where the specified data will
be read from.
STR
$
SHFT
ANDST
L
3
D
SHFT
JMP
K
SHFT
ANDST
L
3
D
ANDN
W
SHFT
STRN
SP
1
B
1
C
6
E
ENT
1
B
0
A
ENT
SHFT
0
A
5
F
2
C
3
D
0
A
0
A
ENT
SHFT
SHFT
2
C
0
A
0
A
0
A
ENT
SET
X
ANDN
W
SHFT
ANDST
L
3
D
SHFT
JMP
K
0
A
ENT
2
C
5
F
1
B
ENT

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Automationdirect.com DL05 and is the answer not in the manual?

Automationdirect.com DL05 Specifications

General IconGeneral
BrandAutomationdirect.com
ModelDL05
CategoryController
LanguageEnglish

Related product manuals