Appendix A
DL405 Error Codes
Appendix B
Error Codes
B–7
DL05 Error Codes
DL05 Error Code Description
E603
DATA MISSING
A search function was performed and the data was not found.
E604
REFERENCE
MISSING
A search function was performed and the reference was not found.
E620
OUT OF MEMORY
An attempt to transfer more data between the CPU and handheld
programmer than the receiving device can hold.
E621
EEPROM NOT
BLANK
An attempt to write to a non-blank EEPROM in the handheld programmer
was made. Erase the EEPROM and then retry the write.
E622
NO HPP EEPROM
A data transfer was attempted with no EEPROM (or possibly a faulty
EEPROM) installed in the handheld programmer.
E623
SYSTEM EEPROM
A function was requested with an EEPROM in the handheld programmer
which contains system information only.
E624
V-MEMORY ONLY
A function was requested with an EEPROM in the handheld programmer
which contains V-memory data only.
E625
PROGRAM ONLY
A function was requested with an EEPROM in the handheld programmer
which contains program data only.
E626
PROM MC
An attempt to transfer data from a tape to a UVPROM Memory Cartridge.
This transfer must be made using a CMOS RAM Cartridge.
E627
BAD WRITE
An attempt to write to a write-protected or faulty EEPROM in the handheld
programmer was made. Check the write protect jumper and replace the
EEPROM if necessary.
E628
EEPROM TYPE
ERROR
The wrong size EEPROM is being used in the handheld programmer. This
error occurs when the program size is larger than what the HPP can hold.
E640
COMPARE ERROR
A compare between the EEPROM handheld programmer and the CPU was
found to be in error.
E641
VOLUME LEVEL
The volume level of the cassette player is not set properly. Adjust the volume
and retry the operation.
E642
CHECKSUM ERROR
An error was detected while data was being transferred to the handheld
programmer’s Memory Cartridge. Check cabling and retry the operation.
E650
HPP SYSTEM
ERROR
A system error has occurred in the handheld programmer. Power cycle the
handheld programmer. If the error returns replace the handheld programmer.
E651
HPP ROM ERROR
A ROM error has occurred in the handheld programmer. Power cycle the
handheld programmer. If the error returns replace the handheld programmer.
E652
HPP RAM ERROR
A RAM error has occurred in the handheld programmer. Power cycle the
handheld programmer. If the error returns replace the handheld programmer.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Automationdirect.com DL05 and is the answer not in the manual?

Automationdirect.com DL05 Specifications

General IconGeneral
BrandAutomationdirect.com
ModelDL05
CategoryController
LanguageEnglish

Related product manuals