A53 Z0 9 0020 L En Technical documentation
Chapter : Additional functions
13.5
GENSYS 2.0 with external automatic start module
13.5.1
Overview
This chapter describes how to interface GENSYS 2.0 with an engine featuring its own automatic start
module. In this case GENSYS 2.0 internal start sequence must be inhibited. The following diagram shows
the main functions of each device:
Note: starting from firmware v4.00, GENSYS 2.0 features an easy configuration whereas older firmware
versions require the use custom equation(s) (In this case, contact your local distributor or the CRE
Technology technical support).
Figure 58 - Wiring GENSYS 2.0 and Auto Start Module
Genset ready
(optionnal)
(1)
Table 38 - Wiring GENSYS 2.0 and Auto Start Module
(1) See below if your external start module doesn’t have a « Genset Ready » output.
(2) This is only an example. Other GENSYS 2.0 inputs can be used.
Note: The GENSYS 2.0 needn’t the oil pressure and water temperature digital inputs.
Auto Start
Module
Start sequence
Engine protections
GENSYS 2.0
Synchronisation
Electrical protections
GE breaker control
PF control
kW control
Monitoring
Oil pressure
Water temperature
Pickup