A53 Z0 9 0020 L En Technical documentation
Chapter : Text file & PLC
141
All the parameters (Variable from 1000 to 1999 and from 4000 to 4999) of the module are stored in a non-
volatile FLASH memory within the module. It is possible to download or upload these parameters with a
computer, thus allowing the user to save, modify and reuse these parameters later.
All these values are stored in a text file. The following chapter describes the layout of the file.
The file can be exchanged between a PC and module, as described in §17.4.6 and §17.4.7. It can also be
exchanged with the SD card as described in §15.7.3 .
14.3
Text file description
The complete module configuration can be contained in a simple text file. This file can be downloaded from
the module to be kept on a computer. It can also be manually edited on a computer and sent to a module
to fully setup this module in a single step.
This text file is made up of 5 different blocks:
Parameter values.
Label definitions.
Unit definitions.
PLC initializations.
PLC equations.
14.3.1
Generating an empty text file template
The module can generate an empty template that contains the minimum requirement to write
custom equations.
This can be done either:
1. By a computer connection to the embedded Web site in “System/GENSYS 2.0 -> PC file” menu (See
§17.4.6 for more details)
1. By the front panel LCD using an SD card in System/Communication ports config./COM6(SD CARD)”
menu (See §15.7.3 for more details).
14.3.2
Parameter definition block
The starting point of this block is designated by a "{PARAMETERS}" statement.
Each parameter (1xxx or 4xxx variable) can be found as an input in this block. The structure of the input is
as follows:
The variable parameter number preceded by the letter V (Ex: V1006)
The value (Ex: 320)
R/W attribute (for MODBUS and PLC equations) (Ex: Y)
The label (only for clarification) (Ex: Gen Nominal kW)
The minimal value (only for clarification) (Ex: +00000)
The maximal value (only for clarification) (Ex: +65535)
Ex:

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CRE Technology GENSYS 2.0 and is the answer not in the manual?

CRE Technology GENSYS 2.0 Specifications

General IconGeneral
BrandCRE Technology
ModelGENSYS 2.0
CategoryControl Unit
LanguageEnglish

Related product manuals