A53 Z0 9 0020 L En Technical documentation
Chapter : Menu overview
217
Parameter
[var.num]
Comment
Crank relay
[E1989]
Function of the A1 output.
Fuel relay
[E1916]
Function of the A2 output.
Table 101 Relay outputs configuration
Notes :
If E1916= "Unused" the default parameter are used, with[E2019] set on A1 output (Fuel).
If E1989= "Unused" the default parameter are used, with [E2018] set on A2 output (Crank).
The polarity can’t be changed on these outputs.
3/ Breakers
This menu is used to set the breakers configuration (generator and mains). Each breaker can be configured
with one of the 6 values below (see §10.4.1 for more details)
0 =
Open contact
Close pulse
1 =
Open contact
Close contact
2 =
Open MXcoil
Close pulse
3 =
Open MXcoil
Close contact
4 =
Open pulse
Close pulse
5 =
Open pulse
Close contact
Table 102 Breakers configuration
Mains brk ctrl [E1992]: Mains breaker control.
GE brk ctrl [E1993]: Generator breaker control.
4/ Expansion outputs
To configure the expansion, outputs, the CRE Config software must be used.
For more details on the expansion outputs configuration, see chapter §15.3.1.