A53 Z0 9 0020 L En Technical documentation
Chapter : Communication
178
3/ MDEC

GENSYS 2.0 wiring
Figure 83 - MDEC: GENSYS2.0 connexion
Label
GENSYS 2.0
terminal
MDEC X1
connector
X003
connector
Digital output to stop request and
emergency stop
C1
h
25
g to ground
26 to ground
Digital output to start request
C2
N
43
M
44 to ground
CAN High
COM 2 pin 7
G
49
CAN Low
COM 2 pin 2
F
50
CAN ground
COM 2 pin 5
E
51
Analogue speed command
G9
AA
8
Analogue speed reference
G11
b
31 (5V ref)
Table 70 - MDEC connexion
Useful GENSYS 2.0 parameters are listed below to ensure proper communication with the MDEC module:
Variable
number
Label
Value
Description
V1076
ESG amplitude
50.0
Speed output amplitude to have a trip frequency of +/-
3Hz.
V1077
ESG offset
0.00
Offset to obtain nominal frequency.
V1156
Local language
3
Custom language selected for MDEC labels on the
GENSYS 2.0 screen.
V1311
PC language
3
Custom language selected for MDEC labels on your PC.
V1710
User param 001
10
Time to stop request on digital output C1 (1.0 sec. here)
V1711
User param 002
1500
Nominal speed for MDEC through CAN bus.
V1712
User param 003
300
Delay (*100ms) before triggering an MTU CAN bus error.
(30 seconds here).
V1852
Branch P-oil
352
The Analogue oil pressure that comes from the MTU CAN
bus will be used.
(1)
X003
connector
h
g
N
M
MDEC
G
F
E
AA
b
C1
C2
GENSYS 2.0
COM2 / 7
COM2 / 2
COM2 / 5
G9
G11
25
26
43
44
49
50
51
8
36
31
0V
0V