A53 Z0 9 0020 L En Technical documentation
Chapter : Text file & PLC
14.7
GENSYS 1.0 – GENSYS 2.0 compatibility
Using a GENSYS 1.0 configuration file in a GENSYS 2.0 unit is a risky operation and requires excellent
knowledge of the parameters and equations transferred.
New functions have been added to the GENSYS 2.0 which use new variables. Certain GENSYS 1.0 variables
have been redefined with new functions in the GENSYS 2.0.
The digital input variables have been moved:
E2004 becomes E2804
E2005 becomes E2805
...
E2015 becomes E2815
The references for GENSYS 1.0 variables E2004 to E2015 must be replaced with variables E2804 to E2815 in
all the equations which will be introduced to the GENSYS 2.0.
A timer may now be associated to these variables by using variables E1998, E1999 and E1277 to E1286.
Special care must be taken with the following parameters if used in the GENSYS 2.0. Also check the
read/write authorisation (Y/N) which is associated with each parameter:
V1013 0 N J1939 sc adres +00000 +65535
V1017 60 N J1939err delay +00000 +65535
V1149 5.0 N Fail to O/C br +0000.0 +6553.5
V1476 0 N Div D ILS +00000 +65535
V1504 0 N Div D Q share +00000 +65535
V1517 1 N RESET delay +00000 +65535
V1596 125 N CAN Speed +00000 +65535
V1633 60 N Fail to start +00000 +65535
V1852 29 y Branch P-oil +00000 +65535
V1853 30 Y Brnch T-water +00000 +65535
V1854 33 Y Branch Speed +00000 +65535
V1855 0 Y Com2 protocol +00000 +65535
V1856 17 Y J1939 Address +00000 +65535
V1857 0 Y CT speed + +00000 +65535
V1858 0 Y CT Oil Pres - +00000 +65535
V1859 0 Y CT Cool Temp + +00000 +65535
V1860 0 Y CT Oil Pres -- +00000 +65535
V1861 0 Y CT Cool Temp++ +00000 +65535
V1862 0 Y CT speed ++ +00000 +65535
V1863 0 Y CT Malfonction +00000 +65535
V1864 0 Y CT Protection +00000 +65535