EasyManua.ls Logo

CRE Technology GENSYS 2.0 - Phase Offset (Dyn11 and Other); Figure 73 - Phase Offset Example

CRE Technology GENSYS 2.0
244 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A53 Z0 9 0020 L En Technical documentation
Chapter : Additional functions
136
To deactivate the outputs, it is necessary to reset the alarm [E2729] on the front panel.
13.16
Phase offset (Dyn11 and other)
13.16.1
Introduction
This advanced function, available with option 8, provides a choice of phase offset [E1929] between mains
and generator voltage measurement. That means that GENSYS 2.0 will command the breaker to close with
the selected phase angle shift.
Figure 73 - Phase offset example
13.16.2
Settings
The phase offset modification can be done via the configuration menu synchronization check relay
17.3.9) by using the [E1929] parameter.
The Phase offset [E1929] can be chosen from the following values: 0°, +30°, +60°, +90°, +120°, +150°, 180°,
-30°, -60°, -90°, -120° and -150°.
A modification of this parameter can be done only when the generator is stopped. Moreover a
confirmation page will be displayed when modified the phase offset.
Note: After choosing your phase offset, you can lock this value by disabling the option 8.
You must take care before choosing this function and modifying the phase offset parameter.

Table of Contents

Related product manuals