A53 Z0 9 0020 L En Technical documentation
Chapter : Communication
187
3/ Modbus communication example:
Table below gives an example of a MODBUS master sending a reading request (function 04) of 3 registers
starting from variable E0007. This request is sent to a GENSYS 2.0 setup as slave number 5.
MODBUS RTU request/answer example
Master request
GENSYS 2.0 slave answer
Field
Value
Field
Value
Slave address
05
Slave address
05
Function request
04
Function
04
Starting register (MSB)
00
Data bytes (=2*Number of requested registers)
06
Starting register (LSB)
07
Value of register E0007 (MSB)
D0
Number of registers (MSB)
00
Value of register E0007 (LSB)
D1
Number of registers (MSB)
03
Value of register E0008 (MSB)
D2
CRC16 (MSB)
00
Value of register E0008 (LSB)
D3
CRC16 (LSB)
4E
Value of register E0009 (MSB)
D4
Value of register E0009 (LSB)
D5
CRC16 (MSB)
XX
CRC16 (LSB)
YY
Table 77 - Modbus communication example

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CRE Technology GENSYS 2.0 and is the answer not in the manual?

CRE Technology GENSYS 2.0 Specifications

General IconGeneral
BrandCRE Technology
ModelGENSYS 2.0
CategoryControl Unit
LanguageEnglish

Related product manuals