A53 Z0 9 0020 L En Technical documentation
Generator electrical fault
This menu allows to set the parameters used when a generator electricalfault occur. (See §13.4 for more
details)
Delay before the generator tries to re-synchronize with Mains
after a "Generator electrical fault"
Number of attempts to re-synchronize
Table 86 - Generator electrical fault Configuration
Note :
In case of a generator electrical fault, the generator breaker is opened and the GENSYS 2.0 is in state 40. In
this state the alternator is de-excited (if wired) during a delay [E1265]. After this delay, if the fault is still
present there is a hard shut down; otherwise GENSYS 2.0 tries to re-synchronize.
AVR control
This menu allows to set the AVR control. (See §10.3 for more details)
AVR trip, to be set between 0 and 255.
Output voltage to AVR, to be set between 0 and 255.
Droop sent to AVR if reactive load sharing is undertaken with
droop (if not using inter GENSYS 2.0 CAN bus or in manual mode).
Display the phase-phase voltage U31
Display the sum of the AVR correction signals
Table 87 - AVR control Configuration