A53 Z0 9 0020 L En Technical documentation
Chapter : Menu overview
209
Generator electrical fault
This menu allows to set the parameters used when a generator electricalfault occur. (See §13.4 for more
details)
Parameter
[var.num]
comment
Re-synch delay
[E1843]
Delay before the generator tries to re-synchronize with Mains
after a "Generator electrical fault"
Attempts sync
[E1844]
Number of attempts to re-synchronize
Table 86 - Generator electrical fault Configuration
Note :
In case of a generator electrical fault, the generator breaker is opened and the GENSYS 2.0 is in state 40. In
this state the alternator is de-excited (if wired) during a delay [E1265]. After this delay, if the fault is still
present there is a hard shut down; otherwise GENSYS 2.0 tries to re-synchronize.
AVR control
This menu allows to set the AVR control. (See §10.3 for more details)
Parameter
[var.num]
comment
AVR gain
[E1103]
AVR trip, to be set between 0 and 255.
AVR offset
[E1104]
Output voltage to AVR, to be set between 0 and 255.
Volt droop
[E1105]
Droop sent to AVR if reactive load sharing is undertaken with
droop (if not using inter GENSYS 2.0 CAN bus or in manual mode).
U31
[E0003]
Display the phase-phase voltage U31
AVR output
[E2040]
Display the sum of the AVR correction signals
Table 87 - AVR control Configuration

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CRE Technology GENSYS 2.0 and is the answer not in the manual?

CRE Technology GENSYS 2.0 Specifications

General IconGeneral
BrandCRE Technology
ModelGENSYS 2.0
CategoryControl Unit
LanguageEnglish

Related product manuals