A53 Z0 9 0020 L En Technical documentation
Chapter : Additional functions
GENSYS 2.0 /
CANopen
module
Table 39 - Wiring GENSYS 2.0 TEM
Note: This wiring diagram is only an example; you can use a different wiring setup if necessary.
To start an application, contact your local distributor or CRE Technology support.
13.10
G59 norm (Access level -1)
Access to this specific feature is done using a special procedure:
1. - First connect with password level 1.
- Go in menu “Configuration/Modification by variable n°”
- Set parameter [E1610] on 2
2. - Go back to the login page (press 3 times on [ESC]).
- Enter password « CustMenu ».
- Now you can access to the special features concerning G59
G59 is a protection norm widely used in the UK. You can set and lock the following protections:
Mains Under / Over frequency.
Mains Under / Over voltage.
Vector surge.
ROCOF (df/dt).
When the protections are locked, thresholds, timers and controls are also locked.
13.11
Scada
GENSYS 2.0 communication uses industrial standards. This product is versatile, and can be used with
Modbus, for example to be controlled by a SCADA system.
CRE Technology offers different solutions for such applications (remote display, remote control, event and
alarm management …). Contact us for more information.