A53 Z0 9 0020 L En Technical documentation
11.1.2
Validity
Validity input variable numbers can be set as:
Never active: should be selected if you do not use the input.
Always active: input will be monitored as long as GENSYS 2.0 has power.
Input will be monitored at the end of the "safety on delay” [E1514]
(1)
Input will be monitored when genset is ready for use.
Input will be monitored as defined in equations.
Table 28 - Input validity domain
(1) Safety ON time configuration is accessible via “Enhanced configuration/Start / stop sequence” menu, on the “Timers” page. Parameter is
configured in [E2192], and counter value is in [E1514].
11.1.3
Direction
For each of the inputs, two options are available:
Table 29 - Input direction domain
11.1.4
Delay
For each input, delay can be defined in 100 ms steps between 0 and 6553 s.
11.1.5
Input functions
Function input variable numbers can be set as indicated in the following table.
Should be selected if you do not use the input.
If the effect of the input activation is
not listed below, choose "used by
equations"
Manual water preheat
request
Can be chosen if a coolant pre heating system is
installed; can be used in conjunction with digital
transistor output. Will only work in manual mode.
Manual oil prelub.
request
Can be chosen if a pre lubrication pump is installed on
the engine; can be used in conjunction with digital
transistor output. Will only work in manual mode.
Can be chosen if pre heating plugs are installed on the
engine; can be used in conjunction with digital transistor
output. Will only work in manual mode.
Should be selected in normal cases unless the input is used for protection.
Normally closed; should be selected if the input is normally connected to 0V and is
opened when active