A53 Z0 9 0020 L En Technical documentation
Chapter : User interface
34
Using Modbus, you can process as follows:
o Write 0 (zero) into parameter [E4066].
o Write 1 (one) into parameter [E4066] to initiate backup.
o Wait 3 seconds and read parameter [E4066]. A value of 2 (two) means that
parameters where successfully saved into FLASH memory.
Note: Parameter [E4066] must first be set as write enabled to be modifiable via Modbus. See Modbus
chapter for more details.
5.3
Remote control using a PC (Ethernet connection)
5.3.1
Compatibility with CRE Config software
Starting from firmware v3.00 GENSYS 2.0 can be monitored and controlled using CRE Config
software. This software features a user friendly interface to monitor measurements and set up
GENSYS 2.0 parameters. You can download CRE Config software from CRE technology Web site
http://www.cretechnology.com. Please refer to CRE Config software documentation for more details.
Figure 10 - CRE Config software
NOTE:
Back-up procedure may take a few seconds. It is thus essential to save parameters while
engine is stopped. NEVER SHUT DOWN YOUR MODULE DURING STORAGE SEQUENCE
(ORANGE LED ILLUMINATED).