A53 Z0 9 0020 L En Technical documentation
3/ Engine/Battery protections
Table 99 – Engine/battery protections configurations
Note: The parameters [E1183] and [E1187] allow to set the protection direction of the spare analog inputs 1
&2. If we considered a maximum threshold or a minimum threshold to not cross: 0 means a maximum
threshold/ 1 means a minimum threshold.
17.3.6
INPUTS
1/ Digital inputs
They are split between the dedicated inputs (J1 to J3) and the configurable inputs (J4 to J5).
For more details on the digital inputs configuration, see chapter §11.1.
2/ Analog inputs
To configure the analog inputs, the CRE Config software must be used.
For more details on the digital inputs configuration, see chapter §11.3.
3/ Expansion inputs
4/ Virtual inputs
Label
The name you give to the virtual input. This will be displayed in the info, alarm, and fault screens if so
programmed.
To configure the expansion, inputs, the CRE Config software must be used.
For more details on the expansion inputs configuration, see chapter §15.3.1.
Virtual digital inputs are designed to offer more features to the end user. They can be
programmed via equations or can copy the status of external (CANopen linked) inputs.
For virtual digital inputs 1 to 40: label, validity, direction, and function have to be defined.
Variable numbers: [E2283 to E2302 and E2565 to E2584]
To configure the virtual inputs, the CRE Config software must be used.