A53 Z0 9 0020 L En Technical documentation
Order output to close generator breaker n°1 upon
startup if the nominal power<E4001
Order output to close generator breaker n°1 upon
startup if the nominal power<E4002
Order output to close generator breaker n°1 upon
startup if the nominal power<E4003
Order output to close generator breaker n°1 upon
startup if the nominal power<E4004
Order output to close generator breaker n°1 upon
startup if the nominal power<E4005
Used to indicate that the generator is ready when using
an external start module. (see §13.5)
Order to synchronize the generator with the mains after
a mains electrical fault (see §13.2)
Table 30 - Input functions
(1) Available only in level 2
11.1.6
Dedicated inputs
In the menu list, each input is named after its pin number on the wiring of GENSYS 2.0. Polarity can be
normally open or normally closed. Program this according to the wiring you will have on site.
As a reminder:
J1 is the Mains breaker state.
J2 is the Genset breaker state.
J3 is the remote start input.
11.2
Digital outputs
Output1 to Output5 are wired on the C connector. These outputs are electronically protected, but not
isolated.
Outputs 1 to 5 (E1260, E1261, E1262, E1262, E1264): function and polarity can be defined.
The "Crank" and "Fuel" relay outputs can be set up for other functions. The initial settings are for "Crank"
and "Fuel". Polarity cannot be changed for these relay outputs. "Crank" output function can be set with
[E1989]; Fuel output function is set with [E1916].
11.2.1
Output configurable functions
To be selected if output is not wired.
To be selected if output is used by
equations.