A53 Z0 9 0020 L En Technical documentation
Note: If your module was setup for DHCP usage on Ethernet, bar graph will stop at 97% even if firmware
was successfully upgraded. Factory parameters inside the new firmware set up the Ethernet to use a fixed IP
address, so this disconnects communication between the module and your computer. You can reset
communication by setting back DHCP configuration for example using the module front panel:
-Activate DHCP in menu « System/Communication ports config. /COM4(ETHERNET) ».
-Switch your module OFF and ON again to initiate DHCP communication.
Otherwise, please see §5.3 in this documentation to setup your computer for communication with factory
setup modules.
15.7.3
Export/Import a TXT file on SD card
These functions are featured starting from firmware v3.00.
1/ Export a text file to SD card
Exporting a TXT file gives you the ability to save parameters and equations of your module into an
SD card. Exporting a TXT file can be done either from the front panel or from the embedded Web
site. Go into menu « System/Communication ports config./COM6(SD CARD)/Module -> SD », then
select “Yes” and click on “Save” button.
Exported file name will be in the form of PARAM00x.TXT. Exact name will be displayed on the
screen. The filename will use the smallest value available. If none is available, then existing file will
be replaced.