A53 Z0 9 0020 L En Technical documentation
Note: Exported content depends on the actual password level. If you entered password level 1, custom level
2 equations that may be running inside your module will not be exported into the TXT file.
2/ Import a text file from SD card
This feature gives you the ability to load parameters and equations from a file on an SD card into
your CRE Technology module. Importing TXT file can be done either from front panel or from the
embedded Web site using menu « System/Communication ports config./COM6(SD CARD)/SD ->
Module ».
File to be loaded must have a name respecting format PARAM00x.TXT
(1)
. Select the file of your
choice and click on « Save » button.
Note: Imported content depends on the actual password level. If you entered password level 1, custom level
2 equations that may be in the TXT file will not be imported.
WARNING:
For safety reasons, parameter E1929 (Phase offset – Used for example with Dyn11
transformers) will not be changed when importing a text file. This parameter must be
adjusted manually.