A53 Z0 9 0020 L En Technical documentation
Chapter : SUPPORT/Troubleshooting
197
kW load sharing is bad
- Check the wiring direction of the current transformers and the power measurements
(“Display/Generator electrical meter/Global view generator” menu). The power by phase must be
balanced and positive.
- Check the speed control is correctly configured and performs the same action on all speed
governors.
- Check that all engines are stable. If one or more engines oscillate in frequency (even slightly), this
oscillation will affect the load sharing.
- Adjust the kW load sharing gain (« Configuration/Control loops/kW control/kW load sharing”
menu)
The breaker control doesn’t work correctly
- Check that the breaker output correspond to the equipment used.
(“Configuration/Outputs/Breakers” menu)
- Check the breaker wiring.
- Check the timers associate to the breaker control. (See §10.4.1)