A53 Z0 9 0020 L En Technical documentation
Chapter : Menu overview
203
If the unit is connected by J1939 to the engine, some extra pages are available in order to display the
measurement received from the engine. (see §15.3.2 for more details)
17.2.6
Inputs/outputs state
1/ Digital inputs 0-7
This menu shows the status of the “Emergency stop” input [E2005] as the status of the 7 first digital inputs
connected on the “J” terminal. [E2000, E2001, E2804 à E2807].
The name of each input is displayed with the status:. Input active =1, Input inactive = 0.
2/ Digital inputs 8-15
This menu shows the status of 8 digital inputs connected on the “J” terminal. [E2808 à E2815].
The name of each input is displayed with the status:. Input active =1, Input inactive = 0.
3/ Relay outputs
This menu shows the status of the 4 relay outputs:
Generator breaker [E2016]
Mains breaker [E2017]
Relay A1 [E2018]
Relay A2 [E2019]
The name of each input is displayed with the status:. Input active =1, Input inactive = 0.
Note: By default, the relay A1 correspond to Crank relay and the relay A2 correspond to Fuel.relay
4/ Digital outputs
This menu shows the status of 5 digital outputs connected on the "C" terminal [E2020 à E2024].
The name of each output is displayed with the status:. Input active =1, Input inactive = 0.
17.2.7
Active timers
This menu shows the timer values running in real time on 2 pages. To change timer values, you should go to
« Configuration/Timers » ( voir §17.3.8).
1/ Timers 1/2
Parameter
[var.num]
comment
Crank timer
[E2060]
Shows the time before crank relay is energized
Warm up timer
[E2061]
Shows the time genset has to wait to warm up before taking the
load.
Speed stab
[E2062]
Shows the time genset has to wait to allow engine speed
stabilization before taking the load.
Volt stab
[E2063]
Shows the time the genset has to wait to allow
voltage stabilization of the engine before taking the load.
Cooling timer
[E2064]
Shows the time the genset has to run without load before
stopping the engine.
Fail to stop
[E2065]
Shows the time of the current stop sequence. If engine does not
stop when this timer

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CRE Technology GENSYS 2.0 and is the answer not in the manual?

CRE Technology GENSYS 2.0 Specifications

General IconGeneral
BrandCRE Technology
ModelGENSYS 2.0
CategoryControl Unit
LanguageEnglish

Related product manuals