A53 Z0 9 0020 L En Technical documentation
Chapter : Precautions
240
Warning:
When you use the virtual digital input in this way: "Generator electrical fault", "Mains
electrical Fault", "External alarm", "External fault (Soft shut down)" or "External security (Hard
shut down)", NEVER use the "Normally Open" or "Normally Close" directions but ALWAYS
"Normally Open Wired Or" or "Normally Close Wired Or".
Warning:
Manual breaker opening.
When an external security device opens the breaker, the order has to be latched. GENSYS 2.0
needs the feedback.
Warning:
When a power plant has several generators, even if only one generator has a GENSYS 2.0, the
number of generators (E1147) must be equal or above 2. If it is 1, you may seriously damage
your generator.
Warning:
The engine, turbine, or other type of prime mover should be equipped with an over speed
(over temperature, or overpressure, where applicable) shutdown device that operates
independently from the prime mover control device.
Warning:
When a power plant has several generators, each GENSYS 2.0 must have a different number
("Genset number" variable: E1179). If two have the same number, there is no conflict but
there will be some operating problems.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CRE Technology GENSYS 2.0 and is the answer not in the manual?

CRE Technology GENSYS 2.0 Specifications

General IconGeneral
BrandCRE Technology
ModelGENSYS 2.0
CategoryControl Unit
LanguageEnglish

Related product manuals