A53 Z0 9 0020 L En Technical documentation
Chapter : Installing and commissioning a GENSYS 2.0 application
9.5.2
Check the protections
Check the 6 minimum protections before carrying out any other tests:
Over speed
Over voltage
Emergency stop
Oil Pressure
Water temp
Reverse kW
9.5.3
Start the generator
In [Manu] mode, press [Start] button.
Check the starter and fuel pump activation.
If you want to simulate the sequences of starter and fuel switching, disconnect the A1 and
A2 terminals, then navigate to the menu "Display/ Inputs/outputs state / Relay outputs" ,
the states of A1 and A2 will be displayed in real time.
When the engine has been started, check the engine speed and the generator voltage.
They must be stable and to the desire value (ex: 1500rpm, 50Hz, 400VAC), these
information are available in the menu “Display/ Generator electrical meter/ Global view
Generator”
Press [Stop] button to stop generator.
9.5.4
Check the control of the dead bus breaker
Start the generator in [Manu] mode by pressing [Start] button.
Press the generator breaker [0/I] key.
The breaker should close (control OK) and the GENSYS 2.0 front face led should light up (feedback
position OK).
Press the generator breaker [0/I] Key.
The breaker should open and the led should go out.