EasyManua.ls Logo

CRE Technology GENSYS 2.0 - Page 71

CRE Technology GENSYS 2.0
244 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A53 Z0 9 0020 L En Technical documentation
Chapter : Installing and commissioning a GENSYS 2.0 application
71
Whatever the power regulation, it’s important to have power on bus in order to check the
currents/voltages/ cos(φ) measurements.
The menu « Display/Generator electrical meter/Global view generator » will allow to check that the
consumed power by phase is positive and balanced. If it’s not the case, check your wiring.
When the power measurement has been check ; the load sharing or constant kW setpoint can be
adjusted by this way :
For a GENSYS 2.0 in load sharing :
In the « Configuration/Control loops/kW control/kW sharing loop » menu, you can adjust
the gain in order to improve the load balanced between GENSYS 2.0 (Adjustment between
0 and 200%)
For a GENSYS 2.0 in kW setpoint (base load or peak shaving), or in load ramp:
In the « Configuration/Control loops/kW control/Ramp/Constant kW » menu, you can
adjust the gain in order to improve the load ramp, or the integral in order to improve the
constant kW setpoint Adjustment between 0 and 200%)
WARNING:
A wrong wiring affecting the power measurements (e.g reverse of current terminals) will
cause a bad GENSYS 2.0 control that can result in an overload or a reverse kW.

Table of Contents

Related product manuals