A53 Z0 9 0020 L En Technical documentation
Chapter : Description
24
4.2.2
Inputs/outputs
Terminal
Description
Terminal
capacity
(mm² / AWG)
Comment
A1
Crank relay out
Output 6
2.5 / 12
Supplied via emergency stop input at battery
positive voltage. Can also be used as configurable
relay output, see §10.4.2
5A max.
A2
Fuel relay out
Output 7
2.5 / 12
Supplied via emergency stop input at battery
positive voltage. Can also be used as configurable
relay output, see §10.4.2
5A max.
A3
Emergency stop
2.5 / 12
To battery positive, normally closed; direct
supply to crank and fuel relay outputs.
B1
Generator N
2.5 / 12
Not necessarily connected.
B2
Generator L1
2.5 / 12
Generator voltage measurement.
100 to 480 V
AC
line to line. Frequency: 50 or 60Hz
nominal, measurement from 35 to 75Hz.
These lines must be protected externally with
100mA/600V
AC
fuses.
B3
Generator L2
2.5 / 12
B4
Generator L3
2.5 / 12
B5
Mains L1
2.5 / 12
Mains voltage measurement.
100 to 480V
AC
line to line. Frequency: 50 or 60Hz
nominal, measurement from 35 to 75Hz.
These lines must be protected externally with
100mA/600V
AC
fuses.
B6
Mains L2
2.5 / 12
B7
Mains L3
2.5 / 12
C1 to C5
Output 1 to 5
2.5 / 12
Transistor output linked to the power supply
voltage (<350mA per output). Over current
protected. Reactive load.
Each output can be configured with a predefined
function or programmed with custom equations,
see details in §11.2.1.
C5 can also be used as a watchdog output (by
default).