A53 Z0 9 0020 L En Technical documentation
Terminal
capacity
(mm² / AWG)
Generator current measurement 0 to 5A.
Maximum rating: 15A during 10s.
1VA consumption.
External current transformers are normally used.
Maximum ratio is 3250 (meaning 3250:1 or
16250:5).
Two configurable relays with one terminal in
common.
Factory setting uses one relay for closing and one
for opening the MAINS breaker.
Isolated contact. 240V
AC
/5A. See also §10.4.1.
Generating set open
breaker
Two configurable relays with one terminal in
common.
Factory setting uses one relay for closing and one
for opening the generating set’s breaker.
Isolated contact. 240V
AC
/5A. See also §10.4.1
Generating set close
breaker
0 to 10kΩ resistive sensors with programmable
gain. See details in §11.3
0 to 10kΩ resistive sensors with programmable
gain. See details in §11.3
Must be used to protect shielded signals.
0 to 400Ω resistive sensors. See details in §11.3