EasyManuals Logo

CRE Technology GENSYS 2.0 User Manual

CRE Technology GENSYS 2.0
244 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #28 background imageLoading...
Page #28 background image
A53 Z0 9 0020 L En Technical documentation
Chapter : Description
28
Terminal
Description
Terminal
capacity
(mm² / AWG)
Comment
K3
Power supply -
2.5 / 12
polarity inversion.
"Power supply -" must be wired from the speed
governor via 4 mm² wires. See "state of the art"
rules wiring diagram.
External 5A / 40V
DC
fuse recommended.
K4
PWM output
2.5 / 12
500Hz PWM output.
Compatible with Caterpillar and Perkins PWM
controlled units. 0-5V protected against short-
circuits to 0V. Details in §10.1.2
L1
Bus/Mains I3+
2.5 / 12
Bus/Mains current measurement.
1 to 5A. Maximum rating: 15A during 10s.
1VA consumption.
External current transformer is normally used.
Maximum ratio is 3250 (meaning 3250:1 or
16250:5).
L2
Bus/Mains I3-
2.5 / 12
L3
Bus/Mains I2+
2.5 / 12
L4
Bus/Mains I2-
2.5 / 12
L5
Bus/Mains I1+
2.5 / 12
L6
Bus/Mains I1-
2.5 / 12
COM1
CAN1
inter GENSYS 2.0
Male DB9
(shielded)
Isolated CAN© bus.
Proprietary protocol to communicate with other
GENSYS 2.0/MASTER 2.0 units and share
data/information.
See details in §15.2.
COM2
CAN2 options
J1939
CANopen
MTU MDEC
Male DB9
(shielded)
Isolated CAN bus (125kb/s factory setting).
See details in §15.3.
Used to communicate with:
remote I/O (see §15.3.1)
J1939 ECU (se §13.3.2)
MTU MDEC protocol (see §15.3.3)

Table of Contents