Chapter 9 Inverter Functions
9-10-3
9.10.3 Externally Tripping the Inverter
 How to force the inverter to shut off output or output an alarm in case of a system error, etc.?
 External trip function assigns the "External fault [EXT]" to an input terminal and turns on that
terminal to generate "External trip error [E12]".
 Use this function when it is necessary to trip the inverter because of an error (trip) signal
generated by a peripheral system, etc.
 When "External trip error [E12]" occurs, the trip cannot be released even when the "External fault
[EXT]" terminal is turned off. Reset the system or turn the power off and back on to release the
trip.
 When the system is reset while [EXT] is still on, [E12] occurs again.
 Restart after reset is determined depending on the setting of "Restart mode after RS release
[C103]". For details, refer to "9.7.5 Starting after Trip Reset or Power-on".
 [E12] occurs when [EXT] is turned on despite the inverter output being stopped.
Code
Item
Description
Data
[C001]
to
[C007]
Input terminal function
External fault [EXT]:
When this signal is turned on, an "External trip
error [E12]" occurs.
12
Free running
ON
ON
ON
RUN command
External fault [EXT] input
Motor speed
Reset [RS] input
Alarm [AL] output
Q
A
!

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi WJ C1 Series and is the answer not in the manual?

Hitachi WJ C1 Series Specifications

General IconGeneral
BrandHitachi
ModelWJ C1 Series
CategoryInverter
LanguageEnglish

Related product manuals