EasyManuals Logo

Hitachi WJ C1 Series User Manual

Hitachi WJ C1 Series
494 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #257 background imageLoading...
Page #257 background image
Chapter 9 Inverter Functions
9-10-5
9.10.5 Avoiding Mechanical Resonance of Motor and Machine
 How to avoid strong vibrations at a certain speed when driving the motor installed in the
system?
 The frequency jump function is used to avoid the resonance points on inverter-driven machines.
 The jump frequency can be set in three locations.
 The output frequency within the range of the jump command varies continuously according to
the normal acceleration/deceleration time.
 When this function is specified, the output frequency cannot be set within the jump frequency
range in order to avoid steady operation within the jump frequency range. A warning appears
when the frequency command set in [F001]/[A020]/[A220]/[A021] to [A035] is within the
frequency range specified in the jump frequency. For details on warnings, refer to "15.3.1
Warning Display".
Code
Item
Description
Data
[A063]
Jump frequency 1
Sets the center of the frequency range you
want to jump. When 0.00 Hz is specified,
the frequency jump function is disabled.
0.00 to 590.00 (Hz)
[A065]
Jump frequency 2
[A067]
Jump frequency 3
[A064]
Jump frequency width 1
Sets 1/2 of the frequency range you want
to jump. The frequency jumps a range of ±
jump width from the jump speed.
0.00 to 10.00 (Hz)
[A066]
Jump frequency width 2
[A068]
Jump frequency width 3
Output frequency
Frequency command
[A063]
[A065]
[A067]
[A064]
[A064]
[A066]
[A066]
[A068]
[A068]
Q
A
!

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi WJ C1 Series and is the answer not in the manual?

Hitachi WJ C1 Series Specifications

General IconGeneral
BrandHitachi
ModelWJ C1 Series
CategoryInverter
LanguageEnglish

Related product manuals