Chapter 12 ProDriveNext/EzSQ
12-2-3
EzSQ program reserved variables and related parameters and I/O terminals
Additional parameters related to EzSQ function are listed below. I/O terminals, analog I/O
terminals, parameters and monitors in the table below input/output to EzSQ program by the
reserved variables shown below.
EzSQ function related monitor
Code
Item
Description
[d023]
Program counter
Displays the number of the program line being
executed.
[d024]
Program No. monitor
Displays the program No. that was set when the
program was created.
[d025]
User monitor-0
Displays the values assigned to Umon(00),
Umon(01), and Umon(02), respectively, in the
program.
[d026]
User monitor-1
[d027]
User monitor-2
Parameters related to EzSQ function
Code
Item
Description
[Ai1] Terminal analog
input
The analog input to [Ai1] terminal is captured to
the general-purpose analog input XA(0).
Parameter setting is not required. The input
characteristic follows the start/end function
([A011] to [A015]). When the parameter is the
initial value, 0 to 10VDC will be 0 to 10000.
[Ai2] Terminal analog
input
The analog input to [Ai2] terminal is loaded to
the general-purpose analog input XA(1).
Parameter setting is not required. The input
characteristic follows the start/end function
([A101] to [A105]). If the parameter is the initial
value, 4 to 20 mA will be 0 to 10000.
[C001]
to
[C007]
Input terminal function
selection
General-purpose input 1 to 7 ([MI1] to [MI7]):
When [MI1] to [MI7] is assigned to an input
terminal, each terminal status is input to the
internal variables X(00) to X(06) (or Xw).
[C021]
[C022]
[C026]
Output terminal
function
General-purpose output 1 to 3 ([MO1] to [MO3]):
When [MO1] to [MO3] is assigned to an
output terminal, the status of the internal
variables Y(00) to Y(02) (or Yw) is output to
the respective terminals.
[C027]
[Ao2] output monitor
selection
When "General-purpose analog output YA(0)" is
set, the value of reserved variable YA(0) is
output from the [Ao2] terminal.
[C028]
[Ao1] output monitor
selection
When "General-purpose analog output YA (1)"
is set, the value of reserved variable YA (1) is
output from the [Ao1] terminal.
[P003]
Pulse input, target
function selection
When "Extension input terminal for EzSQ (02)"
is set, the status of the [PLA] terminal is input to
the internal variable X(07) (or Xw).
[P100]
to
[P131]
EzSQ User parameter
U(00) to U(30)
User parameters U(00) to U(30) can be
read/written from Keypad by [P100] to [P131].
User trip 0 to 9
Code
Item
Description
Trip code
User trip
A user trip can be generated at any timing by
executing trip command from EzSQ program.
[E50] to [E59] occur according to trip 0 to trip
9.
E50 to E59
A