Chapter 18 List of Parameters/Modbus Coil/Register Numbers
18-2-23
Code
Name
Data range
Initial
value
Set
value
Change
during
running
Modbus communication
Page
Register No.
Data Range
Resolution
C163
Input terminal [4]
response time
0 to 200 (× 2ms)
1
14A7h
0 to 200
2
9-15-3
C164
Input terminal [5]
response time
0 to 200 (× 2ms)
1
14A8h
0 to 200
2
C165
Input terminal [6]
response time
0 to 200 (× 2ms)
1
14A9h
0 to 200
2
C166
Input terminal [7]
response time
0 to 200 (× 2ms)
1
14AAh
0 to 200
2
C169
Multistage input
determination
time
0 to 200 (× 10ms)
0
14ADh
0 to 200
10
9-2-7
C900
IRDY action
selection
*3
00: Before WJ200 Ver. 3.0
01: WJ200 Ver. 3.0 or later
01
14CCh
0 to 1
-
-
C901
Overload signal
judgement cycle
selection
*3
00: 40 msec
01: 2 msec
00
14F0h
0 to 1
-
-
C902
Overload signal
filter time
constant
0 to 9999 (ms)
300
14F1h
0 to 9999
1
9-11-3
9-11-4
C903
Overload signal
hysteresis
*3
00.00 to 50.00 (%)
10.00
14F2h
0000 to 5000
0.01
-
*3. This parameter is a dummy parameter. User settings are disabled. Data can be read and written by Modbus
communication, etc.

Table of Contents