Bytes 0…63 Name Type of data Function
Byte 16…19 Max. weight (FSD) DINT/REAL Weight
Byte 20…23 Min. weight DINT/REAL Weight
Byte 24…27 Scale interval DINT/REAL Weight
Byte 28 Exponent USINT Number of decimal places
Example: 1.23 is displayed
Exponent: 2
Byte 29…30 Unit STRING_2 Unit in plain text
"t ", "kg", "g ", "lb"
Byte 31 Reserved
Byte 32…35 Gross filling result DINT/REAL
Byte 36…39 Tare filling result DINT/REAL
Byte 40…43 Net filling result DINT/REAL
Byte 44…47 Set point filling result DINT/REAL
The filling results are stored after filling and
only overwritten when there is a new result.
Byte 48…51 Date of filling result DINT Example:
20161116h corresponds to November 16,
2016
Byte 52…55 Time of filling result DINT Example:
14153199h corresponds to 14:15:31 and
99 ms
Byte 56…59 Sequence number of filling re-
sult
DINT Sequential number
Byte 60 Filling result status BYTE 1 = successful, 2 = tolerance alarm, 3 = can-
celed
Byte 61…62 Reserved
Byte 63 "Last_Error" error The last error number is retained until it is
reset (for possible errors see Chap-
ter
16.6.2).
12.3.5.2.2 Material data
The first 15 bytes and byte 63 (Last_Error) correspond to the layout of the system data.
Bytes 0…63 Name Type of data Function
Byte 0 TableSelect USINT Content of read data:
0 = system data, 1 = material data
X3 Process Indicator PR 5410 12 Fieldbus interface