— 7-5 —
Precautions when the main power and the control power are separately turned on and
off.
When turn on the main power after the control power is on.
◊ Activate the input SVON after the main power is turned on.
When turn off the main power leaving the control power on.
◊ Turn off the main power after deactivation of the input SVON.
The warning P5 (Main AC line under voltage) occurs if the main power is turned off
while the Motor servo is on.
Fig 7-5: Timing when separately turning on and off the main power and the control power
Min 0.5 s
on
off
on
off
Control power
Power
Input SVON
ON
OFF
Min. 0 s