EasyManuals Logo

NSK Megatorque PS Series User Manual

NSK Megatorque PS Series
370 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #342 background imageLoading...
Page #342 background image
— 12-2 —
12.2.1. Power Trouble
Table 12-3: Troubleshooting for power problem
Cause Remedy
1) No control power supplied.
Check the control power voltage at the connector of the Driver
Unit.
2)
CPU is not functioning.
• The power is on but the CPU is not
functioning.
Refer to “CPU Error” in “11.3. Causes and Remedy.”
3) Defective Driver Unit.
If no failure is found in the above checks, the Driver Unit may be
defective. Replace it referring to “Appendix 4: Procedure for
Replacing the EDC Driver Unit.”
12.2.2. Motor Trouble
Table 12-4: Troubleshooting for Motor trouble
Cause Remedy
1)
Wrong combination of Motor and
Driver Unit.
Check if the combination of the Motor and the Driver Unit is
correct.
2) Alarm or warning is occurring. Identify a warning or an alarm.
3)
Overload or mechanical interference
with other part.
The Motor is locked by a part of surrounding mechanism.
Check for mechanical interference with other part of mechanism.
4)
Positioning is not completed.
• (As the sequence of the total System)
The System recognizes that the
previous positioning command is not
executed.
• (In case of a program operation)
executing sequence does not complete
the previous positioning command.)
4-1) Overload or interference with
the equipment into which the
Motor is installed.
• The Motor is not locked, but an
excessive friction load is applied to the
Motor due to the mechanical
interference with the surrounding
mechanism.
4-2) Poor tuning of servo gains
4-3) In the middle of processing a
positioning command.
Executing a positioning command
Executing a program operation
caused by the parameter OE2.
Confirm if the output BUSY is closed or monitor the state of Input
and output by the monitor IO0/RP.
If the BUSY signal is closed, the System is executing a positioning
command.
4-1): Check the mechanical interference with the surrounding
mechanism.
4-2): Refer to “5. Tuning” for adequate tuning.
4-3):
• Wait for completion of the positioning command.
• Terminate the positioning command (such as the command
JOG).
• Input the STP (Stop) command to interrupt the positioning
operation.
5)
No torque output because the
parameter TL is set to zero (TL0).
Check if the parameter TL100 is specified by the ?TL command.
If not, the setting may be altered for some reason. (Normally it
should be TL100.)
Enter TL100 for 100% output torque. (Requires an entry of the
password.
6)
Motor servo is deactivated by the
command MO (Servo off).
Enter the command SV to activate the Motor servo.
7)
The objective program channel is not
selected in a program operation.
Use the command IO0 to confirm if the objective channel is
selected.
8)
Defective Cable, Motor and/or Driver
Unit.
Refer to “Appendix 2: How to Check Motor Condition.” Replace
the cable of the Motor if necessary.
If no failure is found in the Cable and the Motor, the Driver Unit
may be defective. Replace it referring to “Appendix 4: Procedure
for Replacing the EDC Driver Unit.”

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the NSK Megatorque PS Series and is the answer not in the manual?

NSK Megatorque PS Series Specifications

General IconGeneral
BrandNSK
ModelMegatorque PS Series
CategoryEngine
LanguageEnglish

Related product manuals