See the application note “A43Z090100A” to retrieve archives from the BSM II.
The table below list the transmitted variables:
Sum Digital = each bit of this parameter represents a logic variable.
Bit0 = breaker in mains (E2000)
Bit1 = breaker in GE (E2001)
Bit2 Bit14: free
Bit15: forbidden (this bit gives the result a bad negative value)
Note: With this configuration, the BSM II node ID is equal to 1. Make sure that no other device on the
CAN bus has the same node ID.
13.8.4
Custom procedure
This procedure shows you how to customize equations to send your own variables to the BSM II.
See also the application note “A43Z090101A” to customize the BSM II archiving.
Download the text file (level 1 equation) “Z090211a_1.txt” to the GENSYS 2.0 as described in §15.7.3 or
§17.4.7.
Download the text file (level 1 equation) “A43Z090100a_1.txt” to the BSM II.
1/ Change the Node ID of BSM II
See BSM II user's manual to choose the node ID in the BSM II.
Then change this node ID (Output address) in the settings of the GENSYS 2.0 (default ID equal 1) via the CRE
Config software.
2/ Delete message
If you do not need to send all variables set in default equations, you can delete output messages.
To do this, set “Output data type ” to Unused and “Output address” to 0 via CRE Config software.