Chapter 8 Mandatory Setting for Motor Drive and Test Run
8-1-3
■ List of parameters changed when switching to low duty rating
*1. 2nd-motor control [SET] target parameter.
The "Converted value" parameter converts the current setting value at the rated current ratio of
ND and LD.
(e.g.) When ND rated current = 8.0 A/LD rated current = 10.0 A, if the setting 4.0 A at ND mode
is changed to LD mode, it will be converted as follows.
(10/8) × 4.0 A = 5.0 A
(In the case of conversion from LD to ND, it is converted by the inverse ratio shown above.)
When the load rating mode is changed, it may be necessary to set the parameters again. Refer to
the above table and recheck each parameter. Also recheck the parameters related to heat
generation and cooling of the inverter, such as parameters related to torque and current setting,
automatic carrier reduction function, and cooling fan control method selection.
The inverter mode monitor [d060] can be used to check which operation mode is currently
selected.