D2 Series Servo Drive User Manual Drive Tuning
HIWIN MIKROSYSTEM CORP. 6-25
MD07UE01-2005
Figure6.6.2.1 Acceleration feed-forward
Step 4: Record the maximum of Command Current in the acceleration phase, as shown in figure
6.6.2.2. It can be observed from the figure that Command Currentis 16 in the acceleration
phase. When the motor starts moving, Scopewill be shown as figure 6.6.2.2. Use the button
of Toggle scopes windows (Page UP)to change to the graph with a single physical quantity.
Repeatedly clicking this button will switch to the graph of Command Current, Reference
Acceleration, or Position Errorto facilitate the observation of graphic value.
Figure6.6.2.2Trajectory result of motor movement
“Command
Current” is 16.
Reference
Accelerationis
950,000 count/s
2
.
Position Error
is 90 counts.
Toggle
scopes
windows
(Page UP)