Table 66: Parts and Tools Required for Connecting an EX Series Switch to Earth
Ground (continued)
Additional
InformationScrewdriver
Screws and
Washers
Grounding Lug
Specifications
Grounding Cable
Requirements
Earthing
Terminal
LocationSwitch
Phillips (+)
number 2
Two ¼-20 x 0.5 in.
screws with #¼”
split-washer
—provided
Two #¼” flat
washers—
provided
Panduit
LCD2-14A-Q or
equivalent
—provided
6 AWG (13.3
mm²), minimum
60°C wire, or as
permitted by the
local code
Left side of
the chassis
EX8208
See “Special
Instructions
to Follow
Before
Connecting
Earth Ground
to a Switch”
on page 177.
Phillips (+)
number 2
Two ¼-20 x 0.5 in.
screws with #¼”
split-washer
—provided
Two #¼” flat
washers—
provided
Panduit
LCD2-14A-Q or
equivalent
—provided
2 AWG (33.6
mm²), minimum
60°C wire, or as
permitted by the
local code
Two
earthing
terminals:
Left side
of the
chassis
Rear
panel of
the
chassis
EX8216
See
“Grounding
Cable and
Lug
Specifications
for EX9200
Switches” on
page 97.
Phillips (+)
number 2
Two ¼-20 x 0.5 in.
screws with #¼”
split-washer—
provided
Two #¼” flat
washers—
provided
Thomas&Betts
LCN6-14 or
equivalent—
provided
One 6 AWG (13.3
mm²), minimum
60°C wire, or one
thatcomplieswith
the local code
Rear panel
of the
chassis
EX9204
See
“Grounding
Cable and
Lug
Specifications
for EX9200
Switches” on
page 97.
Phillips (+)
number 2
Two ¼-20 x 0.5 in.
screws with #¼”
split-washer—
provided
Two #¼” flat
washers—
provided
Thomas&Betts
LCN6-14 or
equivalent—
provided
One 6 AWG (13.3
mm²), minimum
60°C wire, or one
thatcomplieswith
the local code
Rear panel
of the
chassis
EX9208
See
“Grounding
Cable and
Lug
Specifications
for EX9200
Switches” on
page 97.
Phillips (+)
number 2
Two ¼-20 x 0.5 in.
screws with #¼”
split-washer—
provided
Two #¼” flat
washers—
provided
Thomas&Betts
LCN6-14 or
equivalent—
provided
One 6 AWG (13.3
mm²), minimum
60°C wire, or one
thatcomplieswith
the local code
Rear panel
of the
chassis
EX9214
Copyright © 2017, Juniper Networks, Inc.176
EX9208 Switch Hardware Guide

Table of Contents

Other manuals for Juniper EX9208

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Juniper EX9208 and is the answer not in the manual?

Juniper EX9208 Specifications

General IconGeneral
BrandJuniper
ModelEX9208
CategorySwitch
LanguageEnglish

Related product manuals