— 9-31 —
FZONEA: Function ZONEA
This is to monitor the state of the output ZONEA (Zone A).
◊ Refer to “7.3.1.5. Monitor for Individual Function” for details.
For the monitored state, the parameters ST (Stability timer) and GC (Output logic) in the
command PO (Edit output port) are not applied.
Category Monitor
Format
FZONEA
0
: Not detected
Data range
1
: Detected Zone A
FZONEB: Function ZONEB
This is to monitor the state of the output ZONEB (Zone B).
◊ Refer to “7.3.1.5. Monitor for Individual Function” for details.
For the monitored state, the parameters ST (Stability timer) and GC (Output logic) in the
command PO (Edit output port) are not applied.
Category Monitor
Format
FZONEB
0
: Not detected.
Data range
1
: Detected Zone B
FZONEC: Function ZONEC
This is to monitor the state of the output ZONEC (Zone C).
◊ Refer to “7.3.1.5. Monitor for Individual Function” for details.
For the monitored state, the parameters ST (Stability timer) and GC (Output logic) in the
command PO (Edit output port) are not applied.
Category Monitor
Format
FZONEC
0
: Not detected
Data range
1
: Detected Zone C