11.3 Control the Motor
WARNING
Ensure the enclosure is in place before the device is powered on. Wait for at
least 5 minutes after powering off to allow the DC capacitor being discharged,
and do not remove the cover during this period!
Step Operation Description
1
Rotate the potentiometer counterclockwise
(leftwards) to the greatest extent
Output frequency setting is 0.00
2 Press <Run> button Control command active, 0.00 is displayed
3
Rotate the potentiometer clockwise (right-
wards) slowly till 5.00 is displayed
The motor starts to run
Observe the running status:
If the motor runs in the correct direction
If the motor runs steadily
If there is any abnormal noise or problem
Recommended operation:
Stop the motor immediately by switching off
the power if any abnormality occurs
Restart commissioning only after error cau-
ses have been removed
4 Rotate the potentiometer clockwise The motor accelerates
5 Rotate the potentiometer counterclockwise The motor decelerates
6 Press <Stop> button Stop command activated, the motor stops
7 Check parameters without load Settings according to actual applications
8 Check parameters with load Settings according to actual applications
Tab. 11-5: Motor controlling procedure
After powering on, EFC x610 will generate output if pressing down the <Run>
button (or 'Control by terminals' is activated).
By default, EFC x610 is set as:
The frequency converter is started or stopped by the operating panel.
The output frequency is set by the potentiometer on the operating panel.
After powering on, please confirm:
The setting frequency is displayed (no error display).
The monitoring parameter is consistent with the actual situations.
By default, Output frequency in run status and Setting frequency in stop sta-
tus are displayed as the monitoring parameters, which can be changed to oth-
er parameters with parameters U1.00 and U1.10. The default settings are
based on standard applications with standard motors.
For frequency converters with dust cover, it is recommended to in-
stall an LED panel to perform the above operations.
EFC x610 Series Bosch Rexroth AG
Quick Start
DOK-RCON03-EFC-X610***-IT05-EN-P
95/389

Table of Contents

Other manuals for REXROTH EFC 3610 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the REXROTH EFC 3610 Series and is the answer not in the manual?

REXROTH EFC 3610 Series Specifications

General IconGeneral
BrandREXROTH
ModelEFC 3610 Series
CategoryDC Drives
LanguageEnglish

Related product manuals