12.2.6 I/O Card Terminal Configuration
Set digital input terminals
Code Name Setting range Default Min. Attri.
H8.00 EX1 input
0...46
0 – Stop
H8.01 EX2 input 0 – Stop
H8.02 EX3 input 0 – Stop
H8.03 EX4 input 0 – Stop
Setting range of H8.00...H8.03:
0: No function assigned
1: Multi-speed control input 1
2: Multi-speed control input 2
3: Multi-speed control input 3
4: Multi-speed control input 4
10: Acceleration/deceleration time 1 activation
11: Acceleration/deceleration time 2 activation
12: Acceleration/deceleration time 3 activation
15: Freewheeling stop activation
16: Stop DC-braking activation
20: Frequency Up command
21: Frequency Down command
22: Up / Down command reset
23: Torque / Speed control switch
25: 3-wire control
26: Simple PLC stop
27: Simple PLC pause
30: Second frequency setting source activation
31: Second run command source activation
32: Fault signal N.O. contact input
33: Fault signal N.C. contact input
34: Error reset
35: Forward running (FWD)
36: Reverse running (REV)
37: Forward jog
38: Reverse jog
39: Counter input