12.5.4 Start Behavior Setting
Start mode selection
Code Name Setting range Default Min. Attri.
E0.35 Start mode
0: Start directly
1: DC-braking before start
2: Start with speed capture
3: Automatic start / stop accord-
ing to setting frequency
0 Stop
Start directly
This mode is used in applications with high static friction torque and low load
inertia. The frequency converter runs at [E0.36] 'Start frequency', for [E0.37]
'Start frequency holding time', and then accelerates to setting frequency with
defined acceleration time.
Code Name Setting range Default Min. Attri.
E0.36 Start frequency 0.00...50.00 Hz 0.05 0.01 Stop
E0.37 Start frequency holding time 0.0...20.0 s 0.1 0.1 Stop
Fig. 12-25: Start directly
Set parameter E0.37 'Start frequency holding time' to a non-zero val-
ue when the motor needs to be started with certain start frequency.