Automatic start / stop according to setting frequency
With this function, the converter starts when the setting frequency from analog
input is higher than the threshold, and stops when the setting frequency from
analog input is lower than the threshold. The threshold is set by parameter
E0.41 'Automatic start / stop frequency threshold'.
To use this function, follow the rules below:
The frequency setting source should be set to analog inputs.
The first and second run command source should be set to '0: Panel'.
Code Name Setting range Default Min. Attri.
E0.35 Starting mode
3: Auto start / stop accord-
ing to setting frequency
0 Stop
E0.41
Automatic start / stop frequency
threshold
0.01…[E0.09] Hz 16.00 0.01 Stop
E0.00 First frequency setting source 2: AI1 analog input
3: AI2 analog input
4: EAI analog input
0 Stop
E0.02 Second frequency setting source 2 Stop
E0.01 First run command source
0: Panel
0 Stop
E0.03 Second run command source 1 Stop
Fig. 12-28: Automatic start or stop according to frequency threshold
EFC x610 Series Bosch Rexroth AG
Functions and Parameters
DOK-RCON03-EFC-X610***-IT05-EN-P
157/389

Table of Contents

Other manuals for REXROTH EFC 3610 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the REXROTH EFC 3610 Series and is the answer not in the manual?

REXROTH EFC 3610 Series Specifications

General IconGeneral
BrandREXROTH
ModelEFC 3610 Series
CategoryDC Drives
LanguageEnglish

Related product manuals