● When the setting frequency is higher than [E0.41], the frequency converter
starts and runs to the setting frequency automatically.
– Pressing <Stop> at this time, the frequency converter stops.
– Pressing <Run> again, the frequency converter runs again.
● When the setting frequency is lower than [E0.41], the frequency converter
stops automatically.
● If the threshold [E0.41] is set higher than the setting frequency
high limit [E0.09], the threshold will be limited to the high limit
[E0.09].
● Make sure that:
– The first and the second run command sources are both via
panel.
– The active frequency setting source is via analog inputs.
– The Simple PLC, PID control and Jog function are deactivated.
Otherwise, E0.35 'Starting mode' cannot be set to '3: Auto start /
stop according to setting frequency'. In this case, warning code
'PrSE' will be displayed and the frequency converter keeps in stop
status.