12.9.9 Sleep / Wake Function
This function is used to achieve the maximum extent of energy-saving according
to type of loads in actual applications.
Code Name Setting range Default Min. Attri.
E5.15 Sleep level 0.00...[E0.09] Hz 0.00 0.01 Run
E5.16 Sleep delay 0.0...3,600.0 s 60.0 0.1 Run
E5.17 Sleep boost time 0.0...3,600.0 s 0.0 0.1 Run
E5.18 Sleep boost amplitude 0.0...100.0 % 0.0 0.1 Run
E5.19 Wake up level 0.0...100.0 % 0.0 0.1 Run
E5.20 Wake up delay 0.2...60.0 s 0.5 0.1 Run
The frequency converter may go into the sleep mode when all the conditions be-
low are met:
● [PID feedback] > [E5.19] 'Wake up level'
● [PID output] < [E5.15] 'Sleep level'
● [Duration] t ≥ [E5.16] 'Sleep delay'