E5: Extended function parameters
Code Name Setting range Default Min. Attri.
E5.01
High resolution output current
filter time
5...500 ms 40 1 Run
E5.02 User-defined speed scaling factor 0.01...100.00 1.00 0.01 Run
E5.05 Pump dry protection threshold 0.0 %…[E5.08] 30.0 0.1 Run
E5.06 Pump dry protection delay
0.0…300.0 s
(0.0: Inactive)
0.0 0.1 Run
E5.07 Pump dry protection delay at start-up 0.0…300.0 s 30.0 0.1 Run
E5.08 Pump leakage protection threshold 0.0…100.0 % 50.0 0.1 Run
E5.09 Pump leakage protection delay
0.0…600.0 s
(0.0: Inactive)
0.0 0.1 Run
E5.10 Pump leakage protection delay at start-up 0.0…600.0 s 60.0 0.1 Run
E5.15 Sleep level 0.00...[E0.09] Hz 0.00 0.01 Run
E5.16 Sleep delay 0.0...3,600.0 s 60.0 0.1 Run
E5.17 Sleep boost time 0.0...3,600.0 s 0.0 0.1 Run
E5.18 Sleep boost amplitude 0.0...100.0 % 0.0 0.1 Run
E5.19 Wake up level 0.0...100.0 % 0.0 0.1 Run
E5.20 Wake up delay 0.2...60.0 s 0.5 0.1 Run
Bosch Rexroth AG
Appendix
EFC x610 Series
352/389
DOK-RCON03-EFC-X610***-IT05-EN-P

Table of Contents

Other manuals for REXROTH EFC 3610 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the REXROTH EFC 3610 Series and is the answer not in the manual?

REXROTH EFC 3610 Series Specifications

General IconGeneral
BrandREXROTH
ModelEFC 3610 Series
CategoryDC Drives
LanguageEnglish

Related product manuals