12.4.5 Frequency Setting Saving
With the 'Frequency setting saving' function, unexpected data loss of commis-
sioning or actual application engineering process can be avoided.
Code Name Setting range Default Min. Attri.
E0.06 Digital setting frequency saving mode 0...3 0 – Stop
● 0: Not saved when powered off or stopped
By default, the setting frequency configured by <▲> / <▼> or digital inputs will
not be saved either at power off or frequency converter stop during fine tun-
ing of the setting frequency in the actual application engineering process.
To avoid unexpected data loss of commissioning or actual application engi-
neering process, one of the following three options may be set according to
the actual application conditions:
● 1: Not saved when powered off; saved when stopped
● 2: Saved when powered off; not saved when stopped
● 3: Saved when powered off or stopped