Electric data of EMC filter for 3P 400 VAC models
Description Symbol Unit
0025
-
A-05
0036
-
A-05
0050
-
A-05
0066
-
A-05
0090
-
A-05
0120
-
A-05
0250
-
N-05
0320
-
N-05
Degree of protection
according to IEC
60529
– – IP 20
Listing according to UL
standard (UL)
– – UL 1283
Listing according to
CSA standard (UL)
– – C22.2 No.8
Mass (weight) m kg 1.1 1.75 1.75 2.70 4.20 4.90 5.00 7.20
Mains voltage three-
phase at TN-S, TN-C,
TT mains
U
LN
V 380…480
Mains voltage three-
phase at Corner- groun-
ded-Delta mains
U
LN
V Not allowed
Mains voltage three-
phase at IT mains
U
LN
V Not allowed
Tolerance U
LN
(UL)
– – -15...+10 %
Input frequency (UL)
f
LN
Hz 50...60
Nominal current
I
L_cont
A 25 36 50 66 90 120 250 320
Calculation of leakage
current
I
leak
mA 4.7 4.7 4.7 4.7 5 5 14 14
Required wire size ac-
cording to IEC
60364-5-52; at I
L_cont
A
LN
mm
2
4 10 10 16 35 35 70 120
Required wire size ac-
cording to UL 508 A
(internal wiring); at
I
L_cont
(UL)
A
LN
AWG 10 6 6 6 (2) 1 1 4 / 0
350
kcmil
Tab. 15-6: 3P 400 VAC electric data
EFC x610 Series
Bosch Rexroth AG
Accessories
DOK-RCON03-EFC-X610***-IT05-EN-P
307/389